High Voltage XLPE Insulated Power Cable


CABLE STANDARDS                                                                 
GB/T11017,GB/Z18890,GB/Z22078,IEC and etc. upon request.
 
Specification And Name
1. YJLW02
Power Cable with Copper Conductor, XLPE Insulation, Corrugated Aluminum Sheath, PVC Outer Sheath
2. YJLW02-Z
Longitudinal Water-blocking Power Cable with Copper conductor, XLPE Insulation, Corrugated Aluminum Sheath, PVC Outer Sheath
3. YJLW03
Power Cable with Copper Conductor, XLPE Insulation, Corrugated Aluminum Sheath, PE Outer Sheath
4. YJLW03-Z
Longitudinal Water-blocking Power Cable with Copper Conductor, XLPE Insulation, Corrugated Aluminum Sheath, PE Outer Sheath
5. YJLLW02
Power Cable with Aluminum Conductor, XLPE Insulation, Corrugated Aluminum Sheath, PVC Outer Sheath
6. YJLLW02-Z
Longitudinal Water-blocking Power Cable with Aluminum Conductor, XLPE Insulation, Corru-gated Aluminum Sheath, PVC Outer Sheath
7. YJLLW03
Power Cable with Aluminum Conductor, XLPE Insulation, Corrugated Aluminum Sheath, PE Outer Sheath
8. YJLLW03-Z
Longitudinal Water-blocking Power Cable with Aluminum Conductor. XLPE Insulation, Corrugated Aluminum Sheath, PE Outer Sheath

Operating Environment
1. Max admissible temperature for conductor:
90ºC under normal running condition; 250ºC under short circuit(max. duration is 5s)

2. Min bending radius is recommended to be 20 times of cable overall diameter

3. PVC sheathed cables shall not be installed if the environment temperature is below 0ºC,and if it is below 0ºC,the cable should be heated before the installation

Metal Sheath
1. Cables with corrugated aluminum sheath can be especially suitable for the following conditions in addition to the normal ones
2. Cables with corrugated aluminum sheath: places where there is not much corrosion but much requirement for mechanical strength (e.g. direct connection to transformers, laying on bridges and in vertical shafts)

Plastic Outer Sheath
1. Cables with PVC outer sheath ( Type 02 ) are suitable for high voltage transmission line with general fireproof requirement and centain insulation requirement for the outer sheath

2. Cables with PE outer sheath( Type 03 )are suitable for high voltage transmission line directly buried underground with higher insulation requirement on the outer sheath; and if they are laid in tunnels or vertical shafts, anti-fire and flame-retardant measures must be taken

XLPE Insulation Corrugated Aluminum Sheath For Rated Voltage Of 50/66kV

ConductorNominal thickness of insulation(mm)Aluminium sheath thickness(mm)Non-metallic  thickness(mm)
Norminal Cross-sectional Area(mm²)ShapeApprox.diameter (mm)
240Circular Compacted18.314.02.04.0
30020.614.02.04.0
40023.314.02.04.0
50026.414.02.04.0
63030.114.02.04.0
800Milliken conductor34.814.02.04.0
100038.814.02.34.0
120042.014.02.34.0
140045.214.02.34.0
160048.014.02.34.0
180050.814.02.34.0
200054.014.02.34.0
220057.414.02.34.0
250061.214.02.34.0
 


XLPE Insulation Corrugated Aluminum Sheath For Rated Voltage Of 50/66kV

Norminal Cross-sectional Area(mm²)
 
Approx. Overall diameter
(mm)
Approx.weight of copper cable(kg/km)Approx.weight of copper cable(kg/km)Conductor  D.C resistance at 20ºC     (Ω/km)Cable Capacity   (μF/km)
YJLW02 YJLW02-ZYJLW03
YJLW03-Z
YJLLW02 YJLLW02-ZYJLLW03
YJLLW03-Z
Copper conductorAluminium conductor
24078.069506460546049700.07540.1250.150
30082.076707190581053500.06010.1000.162
40083.088408320639558800.04700.07780.174
50086.0100659510708064200.03660.06050.189
63091.01157010990767070900.02830.04690.207
80097.01445013740934087880.02210.03670.228
1000104.016730160701029096300.01760.02910.260
1200107.0185401787010990103200.01510.02470.268
1400109.0205701986011900112000.01290.02120.285
1600114.0227802207012740120000.01130.01860.298
1800116.0246902395013560128100.01010.01650.311
2000120.0267802603014420136500.00900.01490.326
2200123.0289202813015300145100.00830.01350.342
2500126.0319703116016500156800.00730.01270.359
 


XLPE Insulation Corrugated Aluminum Sheath For Rated Voltage Of 64/110kV

ConductorNominal thickness of insulation(mm)Aluminium sheath thickness(mm)Non-metallic  thickness(mm)
Norminal Cross-sectional Area(mm²)ShapeApprox.diameter (mm)
240Circular Compacted18.319.02.04.0
30020.618.52.04.0
40023.317.52.04.0
50026.417.02.04.0
63030.116.52.04.5
800Milliken conductor34.816.02.04.5
100038.816.02.34.5
120042.016.02.35.0
140045.216.02.35.0
160048.016.02.35.0
180050.816.02.35.0
200054.016.02.35.0
220057.416.02.35.0
250061.216.02.35.0

XLPE Insulation Corrugated Aluminum Sheath For Rated Voltage Of 64/110kV


Norminal Cross-sectional Area(mm²)
 
Approx. Overall diameter
(mm)
Approx.weight of copper cable(kg/km)Approx.weight of copper cable(kg/km)Conductor  D.C resistance at 20ºC     (Ω/km)Cable Capacity   (μF/km)
YJLW02 YJLW02-ZYJLW03
YJLW03-Z
YJLLW02 YJLLW02-ZYJLLW03
YJLLW03-Z
Copper conductorAluminium conductor
24088.084006530694050700.07540.1250.123
30090.090407150721053200.06010.1000.134
40091.098907980748055700.04700.07780.149
50093.0108908910797059900.03660.06050.164
63097.01257010270882065200.02830.04690.183
800104.01514012660994074700.02210.03670.215
1000109.017740151501122086200.01760.02910.233
1200114.019800168401229093300.01510.02470.241
1400117.0219102098013240123100.01290.02120.257
1600120.0241202287514130129700.01130.01860.266
1800122.0254802454014320133900.01010.01650.280
2000126.0272502631014860139300.00900.01490.293
2200129.0304002937016780157500.00830.01350.307
2500133.0330703204017590165700.00730.01270.322

XLPE Insulation Corrugated Aluminum Sheath For Rated Voltage Of 127/220kV

ConductorNominal thickness of insulation(mm)Aluminium sheath thickness(mm)Non-metallic  thickness(mm)
Norminal Cross-sectional Area(mm²)ShapeApprox.diameter (mm)
400Circular Compacted23.327.02.45.0
50026.427.02.45.0
63030.126.02.45.0
800Milliken conductor35.225.02.45.0
100039.524.02.65.0
120042.024.02.65.0
140045.224.02.65.0
160048.024.02.65.0
180050.824.02.85.0
200054.024.02.85.0
220057.424.02.85.0
250061.224.02.85.0
 

XLPE Insulation Corrugated Aluminum Sheath For Rated Voltage Of 64/110kV

Norminal Cross-sectional Area(mm²)
 
Approx. Overall diameter
(mm)
Approx.weight of copper cable(kg/km)Approx.weight of copper cable(kg/km)Conductor  D.C resistance at 20ºC     (Ω/km)Cable Capacity   (μF/km)
YJLW02 YJLW02-ZYJLW03
YJLW03-Z
YJLLW02 YJLLW02-ZYJLLW03
YJLLW03-Z
Copper conductorAluminium conductor
400118.012880120901055097600.04700.07780.144
500121.0142601345011240104300.03660.06050.122
630123.0156701485011740109200.02830.04690.135
800129.0179601710012790119200.02210.03670.154
1000132.0199201904013730128500.01760.02910.170
1200135.0222302132014670137600.01510.02470.180
1400138.0242902336015620146900.01290.02120.190
1600141.0266502569016570159100.01130.01860.198
1800144.0297102860018570174500.01010.01650.205
2000146.0306102962018410174300.00900.01490.213
2200150.0332703172019660185300.00830.01350.223
2500157.0355203446020940198700.00720.01270.234
 

Current-carrying capacity and import factors

Conductor cross-section AreaVoltage level
66 KV110 KV220 KV
Trefoil LayingParallel LayingTrefoil LayingParallel LayingTrefoil LayingParallel Laying
In AirBuriedIn AirBuriedIn AirBuriedIn AirBuriedIn AirBuriedIn AirBuried
240625545650570615535650555----
3007 156 157506457 10605745635----
4008206958657358 10685860720805670850680
50096079010108359367801000826920750985775
63010908901 17095010758601 1559359658501 130880
8001330106014351 1201295103513951090128098513851010
100015151 1851640125014701 150158512251455108015601 130
12001650127518001360160012351730132015851 14017101215
1400178013601955146017351325189014151730120518801290
1600193014452 13515601860140520251505184512602005l;150
18002050150522601640196514702 1601575195012902 1301426
20002 160156524 15172520751635228016552050131022651450
2200226016252560181021801620241517402 165135024001500
2500238017002720191023201680258018202305141025301580
 
Current-carrying capacity and import factors


Conductor cross-section AreaVoltage level
66 KV110 KV220 KV
Trefoil LayingParallel LayingTrefoil LayingParallel LayingTrefoil LayingParallel Laying
In AirBuriedIn AirBuriedIn AirBuriedIn AirBuriedIn AirBuriedIn AirBuried
240485425510445460420505435----
300555480585505550475580496----
400650550680575640540660570625530645550
500750625795660740620790650730605775625
630875715925755860705920745835690905735
8001000805106585098579511058509707801090835
1000113089512209551115885120594011008701190925
1200124096513401030121595513151015120093513051005
1400133510251455110513051015142510851290100514001065
1600142010801555117013901070152011501370103515051130
1800149011201645122014501110160511901420109015901180
2000156511651745127515301155169512501500113016651215
2200164012101840133016051200178513301580117517401235
2500175012701970141017101260191014451695123518401370

XLPE insulated power cable   , xlpe armoured power cable

Assumed conditions for calculating Current-calculating Current:
1. Max. Operating temperature of conductor is 90ºC, and max. short circuit temperature of conductor is 250ºC;
2. single circuit,space between phases is cable diameter plus 70mm;
3. Ambient temperature is 35ºC;
4. Soil thermal resistance of direct butted is 1.0 k.m/W; depth of buried is 1000mm;
5. Earthing method: single point grounding or cross type bonding
Direct buried ambient temperature is influence on current-carrying capacity
Ambient temp10l6202630354045
Influence factor1.071.031.000.960.030.890.840.80
soil thermal resistance coefficient influence on current-carrying capacity
Thermal resistance coefficient0.711 .21 .522.53
.Infinence fautor1.141.000.930.840.740.670.61
Direct buried depth is influence on current-carrying capacity
Depth of direct buried500700900100012001500
Influence factor1.101.051 .011.000.980.95
Air temperature's influence on current-carrying capacity
Air temperature5l0l52025303540455055
Influence factor1.241.211.161.131.081.041.000.960.900 .850.80
Single circuit parallel laying influence on current-carrying capacity
Laying distance(mm)DD+70200250300350400Note:D is cable's overall diameter
Influence factor0.931.001.031.051.071.081.10
 